6.1 Alarm

In the following alarms, relevant LED twinkles, but genset keeps running.
No.
Type
1
Oil filter overtime
2
Fuel filter overtime
3
Air filter overtime
Over battery
4
voltage
Under battery
5
voltage
6
Charging faults

6.2 Time delayed stop alarms

After detecting the time delayed stop alarms, relevant LED twinkles, and genset will be stopped
after a delayed time.
No.
Type
1
Over Current 1
2
Over Current 2
Note: if output configuration is set as "8-Time delayed stop alarms", breaker will be open in
event of over current fault, and genset will be stopped after a delayed time.
When oil filter is overtime than the maintenance value, there will
be an oil filter overtime alarm, maintenance LED
When fuel filter is overtime than the maintenance value, there
will be a fuel filter overtime alarm, maintenance LED
twinkles.
When air filter is overtime than the maintenance value, there will
be a air filter overtime alarm, maintenance LED
When the battery voltage is larger than the set value, battery
LED
twinkles.
When the battery voltage is lower than the set value, battery
LED
twinkles.
When the charging voltage is lower than the set value, battery
LED
twinkles.
If genset current is larger than Over Current 1, over current LED
twinkles, genset will be stopped after a delayed time.
Customers can set values to disable the protection.
If genset current is larger than Over Current 2, over current LED
twinkles, genset will be stopped after a delayed time.
Customers can set values to disable the protection.
- 12 -
KP310V1.0 Controller Operation Manual
Description
Description
twinkles.
twinkles.