Kipor KP310V1.0 Operation Manual page 19

Table of Contents

Advertisement

13
Preheat delay
14
Safety Delay
Generator
Phase Type
15
16
Current Ratio
Under
17
Frequency
18
Over Frequency ○●○○●○
19
Under Voltage
20
Over Voltage
21
Over Current 1
22
Over Current 2
Under
23
Frequency Fault
Delay
Over Frequency
24
Fault Delay
Under Voltage
25
Fault Delay
Over Voltage
26
Fault Delay
Over Current 1
27
Fault Delay
Over Current 2
28
Fault Delay
Over Current 1
29
Stop Delay
Over Current 2
30
Stop Delay
Battery
31
Under Voltage
32
Over Voltage
○○●●○●
0-100
○○●●●○
20-255
○○●●●●
0-4
○●○○○○ 1-65535 1A/5mA
○●○○○●
0-800
0-800
○●○○●●
0-5000
○●○●○○
0-5000
○●○●○● 0-65535
○●○●●○ 0-65535
○●○●●● 0-65535
○●●○○○ 0-65535
○●●○○● 0-65535
○●●○●○ 0-65535
○●●○●● 0-65535
○●●●○○ 0-65535
○●●●○● 0-65535
○●●●●○ 0-65535
○●●●●●
0-400
●○○○○○
0-400
- 17 -
KP310V1.0 Controller Operation Manual
Set Output 1 or Set Output 2 is
setted as " Genset Preheat ", it
0.1s
50
works
controller start to count down..
Within the safety delay, under oil
pressure, high water temperature,
0.1s
60
under speed 、 under voltage 、
under frequency 、 charging fault.
0- 3-Phase 4-Line/3P4L
1- 3-Phase 3-Line/3P3L
1
0
2- 1-Phase 2-Line/1P2L
3- Double voltage
4- Double voltage select
50
External CT ratio
0.1Hz
450
0.1Hz
550
0.1V
2050
0.1V
2450
0.1A
450
Generator pre-overload
0.1A
500
Generator overload
Generator output under frequency
0.1S
20
Stop Delay
Generator output over frequency
0.1S
5
Stop Delay
Generator output voltage low Stop
0.1S
20
Delay
Generator output voltage high
0.1S
5
Stop Delay
Genset pre-overload delay timing
0.1S
600
Genset overload delay timing
0.1S
50
Genset pre-overload stop delay
0.1S
300
timing
Genset overload stop delay timing
0.1S
300
Battery voltage under voltage
0.1V
100
alarm
0.1V
180
Battery voltage over voltage alarm
when
genset
starts,