12. Trouble shooting

Troubles
Controller no electricity
genset Stop
controller emergency stop
Low oil pressure alarm after
start
High water temperature alarm
after start
Alarm & Stop during running
start failure
No start signals
RS232 failure

13. Serial Communication

This communication protocol applies to serial communications between controller and PC, or
between remote controller and display module.
PC and controller meet standard industrial communication protocol in Host and Slave mode. PC
(the Host) sends enquiries, controller (the slave) reply them.
Check batteries
Check controller connections
Check DC fuse
Check if water temperature is over high
Check AC Generator voltage
Check DC fuse
Check if emergency function is OK
Check connections of batteries with emergency stop button
Check if circuits is open
Check oil pressure sensor and connections
Check water temperature sensor and connections
Check relevant connections
Check Set Input parameters
Check fuel pipe and connections
Check batteries
Check RPM sensor and connections
Refer to the Engine's Manual
Check start motor and connections
Check batteries
Check the connections
Check if COM port is right setup
Check connections between RS232 TXD with RXD
Check PC communication port
- 26 -
KP310V1.0 Controller Operation Manual
Solutions