8.2.1.5 Remote start & stop normally open
In the "Remote mode ",After Terminal "8" is closed ( low potential),genset start after remote
start delay(parameters can be setup).Terminal "8" open ( high potential),genset stop after
Remote Stop Delay(parameters can be setup).
8.2.1.6 Remote start & stop normally closed
In the "Remote mode ",After Terminal "8" is open ( high potential),genset start after remote
start delay(parameters can be setup).Terminal "8" close ( low potential),genset stop after
Remote Stop Delay(parameters can be setup).

8.2.2 Set Input

Terminal "13" and Terminal "14" has "self-definition selective input" function ;
KP310_1.00 controller has the following set input function.
No.
0-Warning Normally
1
Open
1-Warning Normally
2
Closed
3
2-Stop normally open
4
3-Stop normally closed
8.2.2.1 Warning Normally Open
After Terminal is closed ( low potential) , Warning alarm. Relevant set input faults LED light up.
After Terminal is open ( high potential), the Set Input faults is eliminated.
8.2.2.2 Warning Normally Closed
After Terminal is open ( high potential) , Warning alarm. Relevant set input faults LED light up.
After Terminal is closed ( low potential), the Set Input faults is eliminated.
8.2.2.3 Stop normally open
After Terminal is closed ( low potential),confirmed by Set Input Fault Delay, stop the alarm
immediately, relevant set input faults LED light up.
Contents
open ( high potential) ;
signal close ( low potential) ;
- 22 -
KP310V1.0 Controller Operation Manual
Note
Normally Open : in the default state, input signal
input signal close ( low potential) is valid;
Normally Closed : in the default state, input
input signal open ( high potential) is valid;