8.2 Programmable output list

8.2.1 Remote set

Terminal "8" has "Remote" function; the function is only valid in "Remote mode".
No.
1
0—Remote start normally
open
1—Remote start normally
2
closed
2—Remote Stop normally
3
open
3—Remote Stop normally
4
closed
4—Remote start & stop
5
normally open
5—Remote start & stop
6
normally closed
8.2.1.1 Remote start normally open
In the "Remote mode ", after Terminal "8" is closed ( low potential), genset start after Remote
start delay(parameters can be setup).Terminal "8" open ( high potential), genset won't stop.
8.2.1.2 Remote start normally closed
In the "Remote mode ",after Terminal "8" is open ( high potential) ,genset start after remote start
delay(parameters can be setup).Terminal "8" close ( low potential), genset won't stop.
8.2.1.3 Remote Stop normally open
In the "Remote mode ",After Terminal "8" is closed ( low potential) , genset won't start.Terminal
"8" open ( high potential),genset stop after Remote Stop Delay(parameters can be setup).
8.2.1.4 Remote Stop normally closed
In the "Remote mode ",After Terminal "8" is open ( high potential) , genset won't start.Terminal
"8" close ( low potential),genset stop after Remote Stop Delay(parameters can be setup).
Contents
open ( high potential) ;
signal close ( low potential) ;
- 21 -
KP310V1.0 Controller Operation Manual
Note
Normally Open : in the default state, input signal
input signal close ( low potential) is valid;
Normally Closed : in the default state, input
input signal open ( high potential) is valid;