7. Wiring

The back panel of KP310V1.0 controller is as follows:
Description of wiring terminals:
No.
Function
1
DC Working power input: B-
2
DC Working power input: B+
3
Emergency stop input
4
Fuel relay output
5
Start relay output
6
Dual voltage selection input
7
Ignition lock start input
8
Remote control input
9
Revolution sensor input +
10
Revolution sensor input -
Water temperature switch
11
input
12
Oil pressure switch input
Programmable configuration
13
input 1
Programmable configuration
14
input 2
15
Charging voltage detect
16
Preheat relay output
17
Programmable relay output 1
31
30
29
28 27 26 25
24
Current
Genset Voltage
(Rated 5mA)
ICOM
IA
IB
A
B
C
N
31
30
29
28
27
26
25
KP310V1.0 GENSET CONTROLLER
1
2
3
4 5
6
7
8
9 10
+
MPU
1 2 3 4 5 6 7 8 9 10
Diameter
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
- 14 -
KP310V1.0 Controller Operation Manual
23 22 21 20 19
IC
24
23
22
21 20
19
11 12 13 14 15 16 17 18
11 12 13 14 15 16 17 18
Note
Connect with the battery cathode
Connect with the battery anode
Connect with B+ with emergency stop button
Rated current:15A, provide B+ by port 3
Rated current:15A, provide B+ by port 3
Active if lower voltage circuit is closed
Connect to the ignition lock start terminal
Remote input terminal, low voltage active
Recommend to connect the revolution sensor
with shielding wire
Connect with water temperature sensor
Connect with oil pressure sensor 连接机油压
力传感器
Provide B+ by port 2
Provide B+ by port 2
Connect with generator D+ terminal
Normal open output, rated current:1A, provide
B+ by port 2
Normal open output, rated current:1A