3. Detailed Settings Function
3. Detailed Settings Function
<Procedure of CZ-RTC3>
[
]
START

How to set the external static pressure

1. Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
2. Press the
or
If you wish to see the next screen instantly, press the
or
button.
Select "8. Detailed settings" on the LCD display and
press the
button.
Maintenance func
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel.
The "Detailed settings" screen appears on the LCD
display.
Select the "Unit no." by pressing the
button for changes.
Detailed settings
Unit no.
3-1
Sel.
Next
3. Select the "Code no." by pressing the
button.
Change the "Code no." to "B0" by pressing the
or
button (or keeping it pressed).
20:30 (THU)
,
and
buttons
20:30 (THU)
Page [
] Confirm
button to see each menu.
20:30 (THU)
Page [
] Confirm
or
20:30 (THU)
Code no.
Set data
B0
0001
or
Detailed settings
Unit no.
3
1 -
Sel.
4. Select the "Set data" by pressing the
button.
Select one of the "Set data" among "0001" – "0015"
according to the desired external static pressure
setting by pressing the
Then press the
(See the table below. For details, refer to the section
"8. EXTERNAL STATIC PRESSURE SETTING" of the
Installation Instructions.)
When setting to auto airflow volume control:
Select the setting data to "-002".
Then press the
Indoor unit
15, 22, 28, 36, 45,
56, 60, 73, 90
External static pressure of the rated air
fl ow volume (Pa)
150
140
130
120
100
70
60
50
30
10
No auto airfl ow volume setting
Auto airfl ow volume setting
5. Select the "Unit no." by pressing the
button and press the
The "Exit detailed settings and restart?" (Detailed
setting-end) screen appears on the LCD display.
Select "YES" and press the
When the setting is completed, perform the test run
for the external static pressure setting described in
"Auto External Static Pressure Setting Operation".
Detailed settings
Unit no.
1-1
Sel.
2-19
2WAY SYSTEM
2WAY SYSTEM
Remote Controller Functions
Remote Controller Functions
20:30 (THU)
Code no.
Set data
B0
0 0
1 0
Next
or
button.
button.
button.
Item code
106, 140, 160
150
140
130
120
110
100
70
50
30
10
button.
button.
20:30 (THU)
Exit detailed settings
Code no.
Set data
and restart?
10
0001
YES
NO
Next
or
1
B0
2
0015
0014
0013
0012
3
0011
0008
0006
0005
0003
4
0001
-001
-002
5
or
6
7
8