3. Auto Address Setting
3. Auto Address Setting
Case 3A

Automatic Address Setting in Heating Mode

Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.
In case of the WHE system, this function does not work properly. Perform
Automatic Address Setting from Outdoor Unit
1.
Perform steps 1 – 4 in the same way as for
Turn the indoor and outdoor unit power ON at all systems.
5.
6.
To perform automatic address setting in
where you wish to set the addresses, short-circuit the automatic address pin (CN30) for 1 second or longer, then release it.
(Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than
one system at the same time.)
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in
Heating mode begins.)
(All indoor units operate.)
1
1
* To cancel, again short-circuit the automatic address pin (CN30) for 1 second or longer, then release it.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the main unit control PCB
turn OFF.)
2
2
7.
At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN30) for 1 second or
longer, then release it.
(Repeat the same steps to complete automatic address setting for all units.)
3
3
8.
Operation from the remote controllers is now possible.
To perform automatic address setting from the remote controller, perform steps 1 – 5, then use the remote controller and
*
complete automatic address setting.
Refer to "Automatic Address Setting from Remote Controller."
4
4
5
5
6
6
7
7
8
8
Case 2
.
, on the outdoor main unit control PCB in the refrigerant system
Heating mode
1-8
1-8
Case 1
Case 2 .
or
2WAY SYSTEM
2WAY SYSTEM
Address Settings
Address Settings

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents