1. Self-Diagnostics Function Table
1. Self-Diagnostics Function Table
• The outdoor unit maintenance remote controller can be used to check the alarm display.
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm display.
(Refer to "Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.")
Alarm code
E06
Outdoor unit failed to receive serial communication signals from indoor unit.
E12
Automatic address setting start is prohibited.
E15
Automatic address setting alarm (too few units)
E16
Automatic address setting alarm (too many units)
E20
No indoor units at automatic address setting.
E24
Outdoor unit failed to receive communications from another outdoor unit.
E25
Outdoor unit address setting failure (duplication)
E26
Mismatch in outdoor unit quantity
E29
Outdoor unit failed to receive communication from another outdoor unit.
E30
Outdoor unit serial communications failure
E31
Communication error between the microcomputers
F04
Compressor 1 discharge temperature sensor trouble
F05
Compressor 2 discharge temperature sensor trouble
F06
Gas temperature sensor trouble at outdoor heat exchanger 1
F07
Liquid temperature sensor trouble at outdoor heat exchanger 1
F08
Outdoor air temperature sensor trouble
F12
Compressor intake temperature sensor trouble
1
F14
SCG temperature sensor trouble
F16
High-pressure sensor trouble
F17
Low-pressure sensor trouble
F22
Compressor 3 discharge temperature sensor trouble
F23
Gas temperature sensor trouble at outdoor heat exchanger 2
2
F24
Liquid temperature sensor trouble at outdoor heat exchanger 2
F31
Outdoor unit non-volatile memory (EEPROM) trouble
H01
Compressor 1 current trouble
H03
Compressor 1 CT sensor disconnected or short-circuit
H05
Compressor 1 discharge temperature sensor disconnected
H06
Low-pressure trouble
3
H08
Compressor 1 oil detection sensor (connection) trouble
H11
Constant speed compressor 2 overcurrent alarm
H12
Constant speed compressor 2 lock current alarm
H13
Compressor 2 CT sensor disconnected or short-circuit
H15
Compressor 2 discharge temperature sensor disconnected
H21
Compressor 3 overcurrent alarm
4
H22
Compressor 3 lock current alarm
H23
Compressor 3 CT sensor disconnected or short-circuit
H25
Compressor 3 discharge temperature sensor disconnected
H27
Compressor 2 lock current alarm
H28
Compressor 3 lock current alarm
H31
HIC trouble alarm
5
L04
Outdoor unit address duplication
L10
Outdoor unit capacity not set
L17
Outdoor unit model mismatch
L18
4-way valve operation failure.
P02
Compressor thermal protector is activated.(trip only and no alarm)
P03
Compressor 1 discharge temperature trouble
6
P04
High-pressure switch activated
P05
Reverse phase (or missing phase) detected, capacity mismatch
P14
O
P16
Compressor 1 overcurrent
P17
Compressor 2 discharge temp trouble
7
P18
Compressor 3 discharge temp trouble
P20
High load alarm
P22
Fan motor trouble
P29
Inverter compressor missing phase or lock alarm
8
sensor is activated.
2
Alarm meaning
5-4
2WAY SYSTEM
2WAY SYSTEM
Self-Diagnostics Function Table
Self-Diagnostics Function Table
(DISCH1)
(DISCH2)
(EXG1)
(EXL1)
(SCT)
(SCG)
(HPS)
(LPS)
(DISCH3)
(EXG2)
(EXL2)
(TO)