3. Mounting to the control panel

3.1 Site selection

This instrument is intended to be used under the following environmental
conditions (IEC61010-1): Overvoltage category
Ensure the mounting location corresponds to the following conditions:
(1) A minimum of dust, and an absence of corrosive gases
(2) No flammable, explosive gases
(3) No mechanical vibrations or shocks
(4) No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 ) that does not change rapidly
(5) An ambient non-condensing humidity of 35 to 85%RH
(6) No large capacity electromagnetic switches or cables through which large
current is flowing
(7) No water, oil or chemicals or where the vapors of these substances can
come into direct contact with the unit

3.2 External dimensions (Unit: mm)

3.3 Panel cutout (Unit: mm)

96
(Fig. 3.2-1)
Caution: If lateral close mounting is used for the controller,
+0.8
□92
0
(Fig. 3.3-1)
, Pollution degree 2
Screw type mounting bracket
Gasket
11.5
(*): When terminal cover is used
+0.5
n×96-3
0
Lateral close mounting
n: Number of units mounted
IP66 specification may be compromised, and all
warranties will be invalidated.
10
Terminal cover
98.5
104.5 (*)