Annual Maintenance; Scheduling Other Maintenance; Operating Log; Maintenance Procedures - Trane RTHC Installation Operation & Maintenance

175-450 ton units (60 hz); 125-450 ton units (50 hz)
Table of Contents

Advertisement

Annual Maintenance

Shut down the chiller once each year to check the
items listed below.
WARNING
Hazardous Voltage! Disconnect all
electrical power, including remote
disconnects before servicing. Fail-
ure to disconnect power before
servicing can cause severe per-
sonal injury or death.
q Perform all weekly and monthly maintenance
procedures.
q Check the refrigerant charge and oil level. Refer
to Section 9 "Maintenance Procedures". Routine
oil changing is not necessary on a hermetic
system.
q Have a qualified laboratory perform an oil analysis
to determine system moisture content and acid
.
level
IMPORTANT: Due to the hygroscopic properties of
the POE oil, all oil must be stored in metal
containers. The oil will absorb water if stored in a
plastic container
q Check the pressure drop across the oil filter. Refer
to Section 9 "Maintenance Procedures".
q Contact a qualified service organization to leak
check the chiller, to inspect safety controls, and
inspect electrical components for deficiencies.
q Inspect all piping components for leakage and
damage. Clean out any inline strainers.
q Clean and repaint any areas that show signs of
corrosion.
q Test vent piping of all relief valves for presence of
refrigerant to detect improperly sealed relief
valves. Replace any leaking relief valve.
q Inspect the condenser tubes for fouling; clean if
necessary. Refer to Section 9 "Maintenance
Procedures".
8 - 2

Scheduling Other Maintenance

q Use a nondestructive tube test to inspect the
condenser and evaporator tubes at 3-year
intervals.
NOTE: It may be desirable to perform tube tests on
these components at more frequent intervals,
depending upon chiller application. This is especially
true of critical process equipment.
q Depending on chiller duty, contact a qualified
service organization to determine when to
conduct a complete examination of the unit to
determine the condition of the compressor and
internal components.

Operating Log

A sample of several operating logs and checklists
have been included. Tablets are available from the
parts department. Refer to Form numbers:
1-27.133(698), 1-27.134(698), 1-27.135(698) and
1-27.136(698)
RTHC-IOM-1C