System Components

Terminal Block TB4

This terminal block is used to connect analog channels L5, L6, L7, and L8.
Pin
Tag Function
1
+V5 Ch-5 positive power supply (250mA max.) to field device
2
-V5
3
+L5 Ch-5 4-20mA input
4
+V6 Ch-6 positive power supply (250mA max.) to field device
5
-V6
6
+L6 Ch-6 4-20mA input
7
+V7 Ch-7 positive power supply (250mA max.) to field device
8
-V7
9
+L7 Ch-7 4-20mA input
10
+V8 Ch-8 positive power supply (250mA max.) to field device
11
-V8
12
+L8 Ch-8 4-20mA input

Grounding the Module

The module must be connected to the system ground using the screw located on the front panel.
3.4.4 Typical Connections
NOTE: If HVAC loss occurs resulting in the ambient temperature to rise above 40°C (104° F),
derate the 250 mA load to 230 mA per channel.
29
Ch-5 negative power supply (8250mA max.) to field device
Ch-6 negative power supply (8250mA max.) to field device
Ch-7 negative power supply (8250mA max.) to field device
Ch-8 negative power supply (8250mA max.) to field device
Figure 3.4 SB-AIM Module Connections
Safety Bus Manual — P/N LS10177-000HI-E:B 02/21/2019