System Components
3.3.2 Visual Indicators
The front panel of the module feature 19 LEDs that indicate the following conditions:
NOTE: During the startup sequence, the yellow and red LEDs blink 3 times, then the seven red
LEDs L1-L7 will go on for 2 seconds to indicate the module address in binary format (L1=1, L2=2,
L3=4, L4=8, L5=16, L6=32, L7=64). At this point, the eight yellow LEDs L1-L8 will begin to blink
rapidly until the module is configured by the panel.
3.3.3 Connections
The SB-SIM/GM module features the following connectors:

Terminal Block TB1

This terminal block supplies power to the module.
Pin
Tag
1
+V
2
+V
3
-V
4
-V

Terminal Block TB2

This terminal block connects the two ring communication links.
Pin
Tag
1
-LK1
2
+LK1
3
SLK1
4
-LK2
5
+LK2
6
SLK2
25
Tag
Color
RUN
Green
LK1-Fault
Yellow
+Leakage
LK2-Fault
Yellow
-Leakage
L1-L8
Red
L1-L8
Yellow
Function
24VDC Power supply positive
24VDC Power supply positive
24VDC Power supply negative
24VDC Power supply negative
Function
Link-1 Negative
Link-1 Positive
Link-1 Screen
Link-2 Negative
Link-2 Positive
Link-2 Screen
M
Mode
Condition
O
On Solid
Normal operation
Off
Module failure or no power
O
Off
Communication on Link LK1 present
Blinking
Link LK1 towards board interrupted
On Solid
Communication failure on Link LK1
Pulsing on/off
Positive earth leakage
O
Off
Communication on Link LK2 present
Blinking
Link LK1 towards board interrupted
On Solid
Communication failure on Link LK2
Pulsing on/off
Negative earth leakage
O
Off
Channel in normal state
Blinking
Channel in pre-alarm
On Solid
Channel in alarm
O
Off
Channel in normal state
Blinking
Channel fault (module or line)
On Solid
Channel disabled