3: Connections; 4: Typical Connection - Honeywell H-S81-HS Manual

Safety bus
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

S81-F7011-1 Control Board
3.1.3 Connections
Function
+ Link 1
- Link 1
Link 1 Screen
+ Link 2
- Link 2
Link 2 Screen
+24V (500mA max.)
0V
3.1.4 Typical Connection
V+
V-
F7011-1
T9003-1
TB1
HS-81 Panel Enclosure
+ 24 VDC
- 24 VDC
- LK
+ LK
Ground
Shielding
*Drawing not to scale. All wiring between the Panel, the External Safety Bus Enclosures, and all separately listed regulated UL 864
power supplies (if used) should be within 20 ft (6.096 m) of each other located in the same room with cable in conduit.
Safety Bus Manual — P/N LS10177-000HI-E:B 02/21/2019
E2004-1 Termination
1
+Lk1
4
7
-Lk1
10
13
Sch-
Lk1
16
2
5
8
+Lk1
11
14
-Lk1
17
E2004-1
3
Sch-
Lk1
6
9
12
+24V
15
0V
18
Table 3.1 Field Connections
SB-SIM/GM
T9003-1
T9003-1
TB1
TB1
Figure 3.1 Communication Ring Connections
Multiple-wire Termination
1
Yellow
2
Black
3
Screen
S81/CCT8
1
Yellow
2
Black
3
Screen
S81/CCT8R
SB-SIM
SB-AIM
Safety Bus Enclosure
System Components
SB-NCM
SB-ECM
20