Useful Information

Programming Features Subject to AHJ Approval

This product incorporates field-programmable software. The features and/or options below must be
approved by the local AHJ.
Description
Embedded Logic (ECM Module)
Fault/Disable status of I/Os
Reset inhibition time (ECM module) Yes
Manual discharge delay (ECM
Module)
Hold/Abort Mode (ECM Module)
Discharge delay time after
Hold/Abort is released in Mode C
(ECM Module) Yes
Aut. Discharge delay
9
Permitted
in UL?
Possible Settings
Yes
Does Not prevent
release,
Prevents release
0-30 Minutes,
1-30 Minutes
Yes
0-30 Seconds,
0-60 Seconds
Yes
A,B,C
Yes
Less than 10
seconds,
10 seconds
Yes
0-60 seconds
Programming Features Subject to AHJ Approval
Settings Permitted
in UL 864
Does not prevent
release
0-30 Minutes
Releasing circuits can be reset0
minutes to 30 minutes after
discharge has operated.
0-30 Seconds
C
Continues to count down upon
Abort, but stops and holds at below
10 seconds until release of the
Abort switch. Upon release of the
Abort switch, the time resumes the
countdown at less than 10 seconds.
less than 10 seconds
0-60 seconds
The Automatic Discharge Delay
must be set to a maximum of 55
seconds when releasing devices
utilizing the F7011 communication
ring or F7012 SLC are employed.
Safety Bus Manual — P/N LS10177-000HI-E:B 02/21/2019