Sb-Sim Module; 1: Technical Specifications; 2: Visual Indicators - Honeywell H-S81-HS Manual

Safety bus
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

System Components

3.2 SB-SIM Module

This module can control eight supervised inputs for conventional sensors or detectors with safety-
related functions. This can include automatic, manual, waterflow, and sprinkler supervision
devices. All the channels can be individually reset and are tested every 30 seconds during opera-
tion. It is used to control conventional fire detectors and NO/NC contacts in general.
3.2.1 Technical Specifications
• Number of input channels:
• Wiring:
• Alarm threshold:
• Short-circuit threshold:
• Open Circuit threshold:
• Channel test:
• Power supply voltage:
• Current consumption in stand by:
• Operating temperature:
• Storage temperature:
• Max humidity:
• Protection rating:
• Mounting:
• Dimensions:
• Weight:
• Connections:
• Max. Line Impedance:
• Max. Line Impedance Input Channels 1-8:
• Ground Fault Impedance:
• Max distance between two modules:
3.2.2 Visual Indicators
The front panel of the module features 19 LEDs that indicate the following conditions:
NOTE:
L1-L7 will go on for 2 seconds to indicate the module address in binary format (L1=1, L2=2, L3=4,
L4=8, L5=16, L6=32, L7=64). At this point, the eight yellow LEDs L1-L8 will begin to blink rapidly until
the module is configured by the panel.
21
Tag
Color
RUN
Green
LK1-Fault
Yellow
LK2-Fault
Yellow
L1-L8
Red
L1-L8
Yellow
During the startup sequence, the yellow and red LEDs blink 3 times, then the seven red LEDs
8 individually configurable
Class B Style C
2 programmable thresholds from 4 to 120mA
programmable from 4 to 131mA
1mA
performed every 30 seconds
24VDC
115mA
0 to 49 °C (32 to 120.2 °F)
-55 to 85 °C (-67 to 185°F)
0-95% non condensing
IP30
T35 DIN rail
53 x 167 x 100 (W x H x D mm) (2.1" x 6.6" x 4")
approx. 600g (21 oz.)
2.5mm² removable terminal blocks
20 ft (6.096 m) in the same room, in conduit
50 ohms
</500 ohms
20 ft (6.096 m) in conduit
Mode
Condition
On Solid
Normal operation
Off
Module failure or no power
Off
Communication on Link LK1 present
Blinking
Link LK1 towards board interrupted
On Solid
Communication failure on Link LK1
Off
Communication on Link LK2 present
Blinking
Link LK2 towards board interrupted
On Solid
Communication failure on Link LK2
Off
Channel in normal state
Blinking
Channel in pre-alarm
On Solid
Channel in alarm
Off
Channel in normal state
Blinking
Channel fault (module or line)
On Solid
Channel disabled