• The reset command has not been executed by the panel (Reset)
NOTE: The output that controls secondary discharge is activated immediately following the
activation of the secondary sequence manual operation input without a delay.
Ch-11 EV-Primary/TOA/TO Output
This output can be configured during programming as EV-Primary, TOA or TO.
If configured as EV-Primary, activation occurs as with channel 9.
If configured as TOA or as TO, these outputs are managed as with Type-1 embedded logic.
Ch-12 EV-Secondary/TOA/TO Output
This output can be configured during programming as EV-Secondary, TOA or TO.
If configured as EV-Secondary, activation occurs as with channel 10.
If configured as TOA or as TO, these outputs are managed as with Type-1 embedded logic.

3.8 SB-PRG Programmer

This is a programmer that can be used to set the CAN BUS address of Safety Bus modules.
3.8.1 Technical Specifications
Visualization on an alphanumeric display
Verification/Programming of Safety Bus module addresses
Quick connector for connection to the modules
Membrane buttons
Battery low indicator
9 VDC power supply (with provided alkaline battery)
Current consumption in stand by: 5mA
Operating temperature: -5 - 50 °C (23 - 122°F)
Storage temperature: -30 - 80 °C (-22 - 176°F)
Max humidity: 95% non condensing
49
Safety Bus Manual — P/N LS10177-000HI-E:B 02/21/2019