Behavior Of The Im 151-7 Cpu Depending On The Dp Interface Setting - Siemens SIMATIC ET 200S Manual

Cpu interface module
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

ET 200S in the PROFIBUS Network
Depending on the DP interface setting, the IM 151-7 CPU will behave in the
following way:
Table 4-1
Transmission rate detection
Testing and commissioning
functions
Bus cycle time
Diagnosis via BF LED
Routing (with plugged-in DM
master module)
Maximum data transfer rate and cable length with a PD connecting cable
You can obtain a maximum data transfer rate of 1.5 Mbaud using the PD
connecting cable. The cable length may not exceed 3 meters.
The PD connecting cable should only be connected for an extended period of time
during startup and service.
Data transfer rates over 1.5 MBaud require an active connecting cable for the PD
connection (order number: 6ES7 901-4BD00-0XA0).
4-4

Behavior of the IM 151-7 CPU depending on the DP interface setting

DP Interface of the IM 151-7 CPU
Passive
Yes
Slow
Fast
See Section 7.4
No
ET 200S IM 151-7 CPU Interface Module
Active
No
Fast
Slow
Yes
A5E00058783-04