Siemens SIMATIC ET 200S Manual page 46

Cpu interface module
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Getting Started
Se-
Action
quence
5
Start the Set PD/PC Interface program as described under step 3, point 4. Change the
configuration of the PD/PC interface as follows:
6
Confirm the settings with OK and close the "Set PD/PC Interface" program.
7
Open the front panel of the S7-300-CPU.
Connect the IM 151-7 CPU to the DP interface of the S7-300-CPU using a
PROFIBUS-DP cable. Make sure that the terminating resistor is switched on at both
connectors.
Remove the connector of the PD cable from the MPI interface of the S7-300-CPU and connect
it to the bus connector of the PROFIBUS-DP cable at the S7-300-CPU. Screw on the
connector securely.
Close the front panel of the S7-300-CPU if possible.
8
In the SIMATIC Manager, navigate to the block
container of the ET 200S.
Select the block container in the left-hand side of
the window.
In the PLC menu of the SIMATIC Manager, select
the Load command to transfer the program and the
hardware configuration to the IM 151-7 CPU.
Confirm all windows that appear with Yes.
2-20
Result
The program and configuration are
downloaded from the PD to the
IM 151-7 CPU.
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04