11. CONNECTION OF ThE POWEr CIrCUITs

Source supply side
It is essential to tighten all used terminals, with cables and/or bridging bars, before use.

11.1. ratings / cross-sections table of correspondence

Min cable size
2
recommended (mm
)
**Max cable size
2
recommended (mm
)
*With extension unit.
** Maximum cable size for rigid cable is 50 mm
Not compatible with aluminium cables
ATyS t M - 542 931 C - SOCOMEC
Hexagonal Metric
Allen size 4
5,0 Nm
10 to
70 mm²
15mm
40 A
63 A
10
16
50
50
. For larger terminations use the power connection terminals ref. 1399 4017.
2
80 A
100 A
25
35
50
50
125 A
160 A
50
50
70*
70*