Carel pCO Manual page 32

Standard 1/3 compressor pack control
Hide thumbs Also See for pCO:
Table of Contents

Advertisement

M_SERVIZIO3
+--------------------+
¦Alarm relay
¦delayed for
000 sec¦
¦
¦
+--------------------+
Digital output no. 10 can be used to signal any alarm condition. The Operator will be informed of
the off-normal condition after the time-delay selected in this mask.
M_SERVIZIO4
+--------------------+
¦Compressors
¦Time among two req.:¦
¦Start
0000 sec¦
¦Stop
0000 sec¦
+--------------------+
This mask allows you to set the time-interval between two consecutive requests for compressors
ON/OFF.
M_SERVIZIO5
+--------------------+
¦Compressor
¦Minimum time of:
¦Start
0000 sec¦
¦Stop
0000 sec¦
+--------------------+
This mask allows you to set the minimum time-interval relative to each ON and OFF routine of the
same compressor.
M_SERVIZIO6
+--------------------+
¦Compressor
¦Time among following¦
¦starts of the same
¦compressor.
000 sec¦
+--------------------+
This mask allows you to set the time-interval relative to consecutive ON routines of the same
compressor.
M_SERVIZIO7
+--------------------+
¦Fans
¦Time among following¦
¦starts
000 sec¦
¦
+--------------------+
This mask allows you to set the time-interval between two consecutive requests for fans ON.
M_SERVIZIO8
+--------------------+
¦Supervisor call:
¦Enabled:
¦Hour
¦
+--------------------+
Ver. 1.0 dated 21/10/94
AL¦
¦
¦
AL¦
AL¦
¦
AL¦
¦
AL¦
¦
AL¦
N ¦
00:00¦
¦
32