5 How to Install
5.5.3 F Frame Circuit Breakers
Frame size
F3
F4
F4
F4
* Drive SCCR rating maybe less than 100 kA when this option is added. See the drive label for SCCR rating.
5.5.4 F-Frame Mains Contactors
5
Frame size
F3
F3
F3
F4
F4
* Drive SCCR rating maybe less than 100 kA when this option is added. See the drive label for SCCR rating.

5.6 Final Set-Up and Test

To test the set-up and ensure that the frequency converter is running, follow these steps.
Step 1. Locate the motor name plate.
Step 2. Enter the motor name plate data in this parameter list.
To access this list first press the [QUICK MENU] key then select "Q2 Quick
Setup".
1.
Motor Power [kW]
or Motor Power [HP]
2.
Motor Voltage
3.
Motor Frequency
4.
Motor Current
5.
Motor Nominal Speed
146
Power & Voltage
P450 380-500V & P630-P710 525-690V
P500-P630 380-500V & P800 525-690V
P710 380-500V & P900-P1M0 525-690V
P800 380-500V
Power & Voltage
P450-P500 380-500V & P630-P800 525-690V
P560 380-500V
P630380-500V
P900 525-690V
P710-P800 380-500V & P1M0 525-690V
par. 1-20
par. 1-21
par. 1-22
par. 1-23
par. 1-24
par. 1-25
MG.20.N5.02 - VLT
Type
Merlin Gerin NPJF36120U31AABSCYP*
Merlin Gerin NRJF36200U31AABSCYP*
Merlin Gerin NRJF36200U31AABSCYP*
Merlin Gerin NRJF36250U31AABSCYP*
Type
Eaton XTCE650N22A*
Eaton XTCE820N22A*
Eaton XTCEC14P22B*
Eaton XTCE820N22A*
Eaton XTCEC14P22B*
NB!
The motor is either star- (Y) or delta- connected (Δ).
This information is located on the motor name plate
data.
®