3 VLT AQUA Selection

3.2 Efficiency

Efficiency of VLT AQUA (η
The load on the frequency converter has little effect on its efficiency. In general, the efficiency is the same at the rated motor frequency f
motor supplies 100% of the rated shaft torque or only 75%, i.e. in case of part loads.
3
This also means that the efficiency of the frequency converter does not change even if other U/f characteristics are chosen.
However, the U/f characteristics influence the efficiency of the motor.
The efficiency declines a little when the switching frequency is set to a value of above 5 kHz. The efficiency will also be slightly reduced if the mains
voltage is 480 V, or if the motor cable is longer than 30 m.
Efficiency of the motor (η)
The efficiency of a motor connected to the frequency converter depends on magnetising level. In general, the efficiency is just as good as with mains
operation. The efficiency of the motor depends on the type of motor.
In the range of 75-100% of the rated torque, the efficiency of the motor is practically constant, both when it is controlled by the frequency converter
and when it runs directly on mains.
In small motors, the influence from the U/f characteristic on efficiency is marginal. However, in motors from 11 kW and up, the advantages are significant.
In general, the switching frequency does not affect the efficiency of small motors. Motors from 11 kW and up have their efficiency improved (1-2%). This
is because the sine shape of the motor current is almost perfect at high switching frequency.
Efficiency of the system (η
To calculate the system efficiency, the efficiency of VLT AQUA (η
η
) = η
x η
SYSTEM
VLT
MOTOR
Calculate the efficiency of the system at different loads based on the graph above.
3.3 Acoustic noise
The acoustic noise from the frequency converter comes from three sources:
1.
DC intermediate circuit coils.
2.
Integral fan.
3.
RFI filter choke.
The typical values measured at a distance of 1 m from the unit:
Enclosure
A2
A3
A5
B1
B2
B3
B4
C1
C2
C3
C4
D1+D3
D2+D4
E1/E2 *
E1/E2 **
F1/F2/F3/F4
* 315 kW, 380-480 VAC and 450/500 kW, 525-690 VAC only!
** Remaining E1+E2 power sizes.
*** For D, E and F sizes, reduced fan speed is at 87%, measured at 200 V.
54
)
VLT
MOTOR
SYSTEM
VLT
At reduced fan speed (50%) [dBA] ***
MG.20.N5.02 - VLT
) is multiplied by the efficiency of the motor (η
51
51
54
61
58
59.4
53
52
55
56.4
-
74
73
73
82
78
®
is a registered Danfoss trademark
®
VLT
AQUA Drive Design Guide
, even if the
M,N
):
MOTOR
Full fan speed [dBA]
60
60
63
67
70
70.5
62.8
62
65
67.3
-
76
74
74
83
80