CNT-SVX05A-EN

Input/output summary

The controller includes the following input and
output points:
Power
24VAC NEC Class 2
Two binary outputs
Supply fan start/stop (BO 1)
Exhaust fan start/stop (BO 2)
Five analog outputs
Supply fan speed (AO 1)
Cool output (AO 2)
Heat output (AO 3)
Face and bypass damper (AO 4)
Outdoor air damper (AO 5)
Seven analog inputs
Space temperature (IN 1)
Local setpoint (IN 2)
Fan mode switch (IN 3)
Discharge air temperature (IN 4)
Outdoor air temperature (IN 5)
Mixed air temperature (IN 6)
Duct static pressure (J43)
Six binary inputs
Low temp detect (IN 7)
Run/stop (IN 8)
Occupancy or generic (IN 9)
Supply fan status (IN 10)
Filter status (IN 11)
Exhaust fan status (IN 12)
Timed override On and Cancel inputs
Comm5 communication