Binary Inputs - Trane Tracer AH.540 Installation Owner Diagnostics

Configurable air handling unit controller
Hide thumbs Also See for Tracer AH.540:
Table of Contents

Advertisement

CNT-SVX05A-EN

Binary inputs

The default configuration for each binary input (including normally open/closed)
of the Tracer™ AH.540 is set at the factory. For field-installed AH.541 controllers,
the configuration of the binary inputs must be set with Trane Rover
software.
Configure any binary input not in use (an input to which no device is physically
connected) as Not Used.
The Tracer AH.540 controller has six available binary inputs. The binary inputs
are connected to the Tracer AH.540 terminal board on inputs IN 7 through IN 12.
Normally these inputs are factory-configured for the following functions.
Binary inputs
• IN 7: Low temperature detection (freezestat)
• IN 8: Run/stop
• IN 9: Occupancy or generic
• IN 10: Supply fan status
• IN 11: Filter status
• IN 12: Exhaust fan status
Configure IN 9 either as Occupancy or as a Generic binary input. When
configured as a generic binary input, IN 9 does not affect controller operation.
Table 8 — Table Binary input controller operation
Binary
Description
Configuration
input
IN 7
Low temp detect
Normally closed Normal
(Note 1)
IN 8
Run/stop
Normally open
(Note 1)
IN 9
Occupancy
Normally open
IN 10
Supply fan status
Normally open
(Note 1)
IN 11
Filter status
Normally open
IN 12
Exhaust fan status
Normally closed Exhaust fan
Note 1: During low temp detect, run/stop, and supply fan status diagnostics, the controller disables all normal unit
operation of the fans, valves, and dampers.
Note 2: The table below shows the controller's response to low temp detect, run/stop, supply fan status, and exhaust
fan status latching diagnostics.
Table 9 — Control response to binary input latching diagnostics
Binary
Latching
Supply
input
diagnostic
fan
IN 7
Low temp detect
Off
IN 8
Run/stop
Off
IN 10
Supply fan status
Off
IN 12
Exhaust fan status Normal
Operation
Note 1: When steam is the source of heat, the heat output is cycled open and closed when the controller is shut down
on a Low Temp Detect latching diagnostic. See Steam valve cycling in the Sequence of operation section for further
details.
Contact closed
Latching diagnostic
(Note 2)
Unoccupied
Normal
Dirty
diagnostic (Note 2)
Cool
Face and
Heat
output
bypass
output
damper
Open
Face
Open
(Note 1)
Closed
Bypass
Closed
Closed
Bypass
Closed
Normal
Normal
Normal
Operation
Operation
Operation
service
Contact open
Latching diagnostic
(Note 2)
Normal
Occupied
Latching diagnostic
(Note 2)
Clean
Normal
Outdoor air
Exhaust
damper
fan
Closed
Off
Closed
Off
Closed
Off
Normal
Off
Operation
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer ah.541

Table of Contents