Test Sequence - Trane Tracer AH.540 Installation Owner Diagnostics

Configurable air handling unit controller
Hide thumbs Also See for Tracer AH.540:
Table of Contents

Advertisement

66
Troubleshooting
Manual output test can be overridden by the following sequences:
• Power up sequence
• Manufacturing test
• Emergency override

Test sequence

The procedure for testing is:
• Press and hold the Test push button for at least two seconds. The green Status
LED turns off, confirming the Test button has been pressed. The Test push
button is located on the right top board edge of the Tracer
• Release the Test button to start the manual output test mode. The manual
output test is then in Step 1. The green Status LED blinks in one of two
patterns. If the Status LED blinks once, no diagnostics are present. If the
Status LED blinks twice, diagnostics are present
• Press the Test button (no more than once per second) to advance through
the test sequence
The manual output test can also be controlled over the communications
network using Rover. When conducting the manual output test via the
communications network, the sequence must start with Step 1 (Off), as shown
in Table 53. However, subsequent steps may be conducted in any order.
Table 54 — Manual output test sequence
Step (Note 1)
Supply fan
1: Off (Note 2)
Off, 0%
2: Supply fan on,
On, 0%
slowest speed (Note 3)
Face and bypass full
face
3: Supply fan on, duct
On, DSP
static pressure control
(Note 5)
4: Cool output open
On, DSP
Outdoor air damper
(Note 5)
open to occupied
minimum position
5: Heat output open
On, DSP
Face and bypass
(Note 5)
full face
Outdoor air damper
open to occupied
minimum position
6: Exhaust fan on
On, DSP
Outdoor air damper
(Note 5)
full open
Face and bypass
full bypass
7: Exit (Note 4)
Note 1: The following diagnostics cause the Tracer AH.540 to exit manual output test:
• Duct Static Pressure High Limit
• Low Supply Fan Air Flow
• Low Temp Detect
• Unit Shutdown
Note 2: Upon entering manual output test mode, all outputs are turned off or closed. The Status LED blinks in a one-
blink pattern in the manual output test, or the Status LED blinks in a two-blink pattern if in the manual output test and
a diagnostic is present.
Note 3: At the beginning of Step 2, the controller attempts to reset all present diagnostics. If the controller is
unsuccessful clearing all diagnostics, the controller exits manual output test.
Note 4: After the last step, the test sequence performs an exit. This initiates a reset and attempts to return the controller
to normal operation.
Note 5: If the controller is configured to operate in variable air volume control, the controller runs duct static pressure
(DSP) control during Steps 3-6.
Note 6: If an exhaust fan status diagnostic occurs, the controller turns off the exhaust fan on this step.
Cool
Heat output Face and
output
bypass
damper
Close
Close
Bypass
Close
Close
Face
Close
Close
Face
Open
Close
Face
Close
Open
Face
Close
Close
Bypass
AH.540 controller
Outdoor air
Exhaust fan
damper
Close
Off
Close
Off
Close
Off
Occupied
Off
minimum
position
Occupied
Off
minimum
position
Open
On
(Note 6)
CNT-SVX05A-EN