CNT-SVX05A-EN
Configuration
Table 34 — Analog inputs
Analog input
Function
(Note 1)
IN 1
Space temperature sensor
IN 2
Hardwired setpoint
IN 3
Fan mode switch
IN 4
Discharge air temp
IN 5
Outdoor air temp
IN 6
Mixed air temp
Duct static
Duct static pressure
Note 1: Trane's Rover service tool uses the unit type to determine and download the proper default analog input
configuration.
Table 35 — Binary inputs
Binary input
Function
(Note 1)
IN 7
Low temp detect or
Not used
IN 8
Run/stop or
Not used
IN 9
Occupancy,
generic or Not used
IN 10
Supply fan status or
Not used
IN 11
Filter status or
Not used
IN 12
Exhaust fan status or
Not used
Note 1: Trane's Rover service tool uses the unit type to determine and download the proper default binary input
configuration.
Note 2: When the supply fan is off, the state of the fan status device is its normal state. For example, if the fan status
switch (end device) is normally open when the fan is off, the controller should be configured for a normally open fan
status input.
Note 3: When the supply fan is off, the state of the filter status device is its normal state. For example, if the filter status
switch (end device) is normally closed when the fan is off, the controller should be configured for a normally closed
filter status input.
Table 36 — Outdoor air damper
Parameter
Occupied outdoor damper minimum position
Occupied standby damper minimum position (Note 1)
Economizer enable temperature (dry bulb)
Low ambient damper lock out temperature (Note 2)
Outdoor air damper open time (Note 3)
Note 1: Occupied standby minimum damper position only applies to space temperature control operation.
Note 2: This is the outdoor air temperature below which the outdoor air damper will always be closed.
Note 3: Adjustable open time for the outdoor air damper to open from 0% to minimum position.
Table 37 — Exhaust fan or damper
Parameter
Exhaust fan start setpoint (Note 1)
Exhaust fan stop differential (Note 1)
Note 1: The exhaust fan is energized when the outdoor air damper is equal to or greater than the exhaust fan start
setpoint. The exhaust fan is turned off when the outdoor air damper is less than the exhaust fan start setpoint minus
the exhaust fan stop differential.
Calibration range
+/-10.0 ° F (+/-5.7°C)
(0.1 ° F resolution)
+/-10.0 ° F (+/-5.7°C)
(0.1 ° F resolution)
NA
NA
NA
NA
NA
Valid range
Default Configuration
Normally open or
Dependent on air handling
Normally closed
unit type
Normally open or
Run/stop
Normally closed
Normally open
Normally open or
Occupancy
Normally closed
Normally open
Normally open (Note 2) or
Sales order dependent
Normally closed (Note 2)
Normally open (Note 3) or
Sales order dependent
Normally closed (Note 3)
Normally open or
Sales order dependent
Normally closed
Valid range
0 to 100%
0 to 100%
32°F to 122°F
(0°C to 50°C)
-40 to 32 ° F
(-40°C to 0°C)
0 to 30 minutes
Valid range
0 to 100%
0 to 100%
Default value
0 ° F
0 ° F
NA
NA
NA
NA
NA
Default value
15%
0%
60 ° F (15.6 ° C)
-20 ° F (-28.9 ° C)
5 minutes
Default value
26%
10%
57