4.3
Installation of the escutcheon for fl ush mounted (to door) applications
- Drill the holes in the enclosure door indicated in the section entitled "Overall dimensions".
- Install the escutcheon (Fig. 8) to the front of the enclosure door. Attach from the inside using self tapping screws (2).
1
Fig. 8
4.4

Heat sink installation (3000A 100% rated only)

Assemble the heat sink on the terminals according to the scheme indicated (Fig.9). Tightening torque 4 Nm - 35,4 lb-in.
Then re-assemble the terminals to the circuit breaker. Tightening torque 40 Nm - 354 lb-in.
Fig. 9
DIR 1000682R0002 Version 03
2
(6)