Circuit Diagrams - Allen-Bradley 140G-R Installation Instructions Manual

Hide thumbs Also See for 140G-R:
Table of Contents

Advertisement

13 Circuit diagrams

WARNING:
Carefully read note F on the circuit diagrams before installing the circuit-breaker.
OPERATING STATE SHOWN
The diagram illustrates the components in the following conditions:
- circuit-breaker open
- circuits de-energized
- releases not tripped
- motor operator with unloaded springs.
VERSIONS
Version without overcurrent release
The applications indicated in fi gure 42 cannot be provided with this version.
KEY
=
Figure number of the diagram
*
=
See note indicated by the letter
K51
=
LSIG-MM electronic release with the following protection functions:
- L overload protection with inverse long-time delay trip setting I1
- S short-circuit protection with inverse or defi nite short time-delay trip setting I2
- I short-circuit protection with instantaneous time-delay trip-setting I3
- G earth fault protection with inverse short time-delay trip-setting I4
M
=
Motor for loading the closing springs
Q
=
Circuit-breaker
AX/1...5
=
Auxiliary contacts of the circuit-breaker
SC
=
Pushbutton or contact for closing the circuit-breaker
SO
=
Pushbutton or contact for opening the circuit-breaker
SO2
=
Pushbutton or contact for opening the circuit-breaker with instantaneous trip
TI/L1
=
Current transformer located on phase L1
TI/L2
=
Current transformer located on phase L2
TI/L3
=
Current transformer located on phase L3
TU
=
Isolation voltage transformer (see note O)
Uaux.
=
Auxiliary power supply voltage (see note F)
UI/L1
=
Current transformer (Rogowski coil) located on phase L1
UI/L2
=
Current transformer (Rogowski coil) located on phase L2
UI/L3
=
Current transformer (Rogowski coil) located on phase L3
UI/N
=
Current transformer (Rogowski coil) located on neutral
W2
=
Serial interface with the accessories of releases LSIG-MM (internal bus)
X1...X7
=
Connectors for the circuit-breaker appications
XK1
=
Connector for the power circuits of releases LSIG-MM.
XO
=
Connector for YO1 release
XR3...XR13
=
Connectors for the auxiliary circuits of releases LSIG-MM.
XV
=
Delivery terminal box for the auxiliary circuits of the circuit-breaker
SNC
=
Shunt closing release
SNT
=
Shunt opening release
EL SNT
=
Overcurrent shunt opening release (trip coil)
UVR
=
Undervoltage release (see notes B and Q)
OUT MM
=
Contact providing MM protection status (Active / Not Active)
DESCRIPTION OF FIGURES
Fig.1
= Circuit of the motor for loading the closing springs.
Fig.2
= Circuit of shunt closing release.
Fig.4
= Shunt opening release.
Fig.6
= Instantaneous undervoltage release (see notes B and Q).
Fig.11
= Contact for electrical signalling of springs loaded.
Fig.13
= Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release.
The circuit-breaker can only be closed after the reset pushbutton has been pressed, or after the coil has
been energized for electrical reset (if available)
Fig.22
= Auxiliary contacts of the circuit-breaker
Fig.42
= Auxiliary circuits of the LSIG-MM release (see note F).
NOTES
B) The undervoltage release is supplied for operation using a power supply branched on the supply side of the circuit-breaker or from an
independent source: the circuit-breaker can only close when the release is energized (there is a mechanical lock on closing).
If there is the same power supply for the closing and undervoltage releases and the circuit-breaker must close automatically when the
auxiliary voltage returns, a 30 ms delay must be introduced between the accept instant of the undervoltage release and energizing of
the closing release. This can be achieved by means of a circuit outside the circuit-breaker comprising a permanent closing contact, the
contact indicated in fi g. 12 and a time-delay relay.
F) The auxiliary voltage Vaux allows all the functions of LSIG-MM releases to be activated.
Since a Vaux isolated from earth is required, it is necessary to use "galvanically separated converters" conforming to standards
IEC 60950 (UL 60950) or equivalent, able to guarantee a common mode current or leakage current (see IEC 478/1, CEI 22/3) of no more
than 3.5mA, IEC 60364-41 and CEI 64-8.
Q) The second shunt opening release may be installed as an alternative to the undervoltage release.
U) The shield of the connection cable must be earthed on the circuit-breaker side only. The connection must be made with shielded two-wire
cable (the BELDEN 3105A type) no more than 15 meters in length.
Z) Short-circuit T5 and T6 if the outside neutral current sensor (UI/N) is not connected.
DIR 1000682R0002 Version 03
(32)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents