7

Instructions for use

7.1

Operating and signalling components

1 Push-button for the manual opening operation
2 Lever for manual loading of the closing springs
3 Mechanical indicator for circuit breaker open "O" and closed "I"
4 Mechanical indicator for protection release tripped
5 Pushbutton for the manual closing operation
6 Indicator for springs loaded - unloaded
7 Operation counter (purchase separately) Catalog No.140-G-R-MOC
8 Key lock on the closing operation (purchase separately) Kirk SD
series cam lock PN-387658 available through Rockwell Automation
Customer Care.
Fig.14
Note
A transparent plastic cover with IP54 (Purchase separately) can be fl ush mounted to the enclosure door. The cover is equipped with a key lock.
Fig. 15
7.2

Circuit breaker closing and opening procedures

Circuit breaker operation can be either manual or electrical.
a) Manual operation for loading the closing springs
– Make sure that "O" (circuit breaker open) is displayed by the indicator
– Make sure that the indicator (6) is WHITE (springs unloaded)
– Repeatedly operate the lever (2) until the color of the indicator (6)
changes to YELLOW
b) Electrical operation for loading the closing springs
Electrical operation of the circuit breaker is possible when the following
accessories are installed:
– charging motor for automatic loading of the closing springs
– shunt closing release
– shunt opening release.
The charging motor automatically reloads the springs after each clos-
ing operation until the yellow indicator appears (6, Fig. 16). If there is
a power failure during the loading operation, the charging motor stops
and automatically continues with the spring loading operation once the
power returns. However, it is always possible to complete the reloading
operation in the manual mode.