GetBatteryStateOfHealth() 0x4F
This read-word command returns the SoH information of the battery in percentage of
design capacity anddesign energy.
Cmd
0x4F
GetBatteryStateOfHealth()
Transfer packet:
22.5 Command Index "Parameter" 0x07
Paramter ID Description
ID
0
Place holder entry. Do not use!
1
Load sensor parameter (values in mA)
2
Maximum backup time (values in seconds)
Countdown timer to shut down the system when power fail occurs (values in
3
seconds). Only on USB.
4
Delay timer between output disable and output enable (value in seconds).
5
Required minimum capacity to enable output (values in percent).
6
Maximum backup time when using analogue read pin.
Single Parameter Data Format:
The data format: AAbbBBccCCddDDEEffFF
ID
AA
Parameter ID (Byte)
BBbb Minimum Value (Uint16)
CCcc Maximum Value (Uint16)
DDdd Standard Value (Uint16)
EE
Is Active (Byte BOOL)
FFff
Value (Uint16)
NOTE: The size of parameter structure is 10 bytes long.
66
Name
0x01 0x03 0x04 0x4F 0x04
Access
Type
R
Uint16
Description
Description
UPSI-1208(D) | UPSI-2406(D)
Min.
Max
Unit
0
65535
mV