GetBatteryDesignCapacity() 0x18
This read-word function returns the nominal capacity.
Cmd
0x18
GetBatteryDesignCapacity ()
Transfer packet:
GetBatteryDesignVoltage() 0x19
This read-word function returns the nominal voltage.
Cmd
0x19
GetBatteryDesignVoltage()
Transfer packet:
GetBatteryManufacturerDate() 0x1B
This read-word function returns the pack's manufacturer date.
Cmd
0x1B
GetBatteryManufacturerDate()
Transfer packet:
NOTE: Value in the following format: Day + Month*32 + (Year–1980)*512
GetBatterySerialNumber() 0x1C
This read-word function returns the assigned pack serial number.
Cmd
0x1C
GetBatterySerialNumber()
Transfer packet:
GetBatteryManufacturerName() 0x20
This read-block function returns the pack manufacturer's name.
Cmd
0x20
GetBatteryManufacturerName()
Transfer packet:
64
Name
0x01 0x03 0x04 0x18 0x04
Name
0x01 0x03 0x04 0x19 0x04
Name
0x01 0x03 0x04 0x1B 0x04
Name
0x01 0x03 0x04 0x1C 0x04
Name
0x01 0x03 0x04 0x20 0x04
UPSI-1208(D) | UPSI-2406(D)
Access
Type
R
Uint16
Access
Type
R
Uint16
Access
Type
R
Uint16
Access
Type
R
Uint16
Access
Type
R
Char[20]
Min.
Max
Unit
0
65535 mAh
Min.
Max
Unit
7000 18000
mV
Min.
Max
Unit
0
65535
-
Min.
Max
Unit
0
65535
-
Min.
Max
Unit
-
-
ASCII