Network Topologies

2.1 Introduction
3
Network Topologies
Which network topologies can be implemented?
The following network topologies can be implemented with the PROFIBUS OLM:
Combinations of these basic types are also possible. To set up the fiber-optic links
of these network topologies, cables with two optical fibers are used.
If a high degree of availability is required of the fieldbus network, this can be
increased by using a redundant network configuration, for example to allow
continued communication if a cable is broken.
Please note the following:
Single DTEs or complete PROFIBUS segments with a maximum of 31 nodes
can be connected to the electrical interface of the PROFIBUS OLM.
Use only fiber-optic cables in areas subject to heavy noise to avoid EMC
problems affecting the entire network.
Only OLMs of the same wavelength may be connected to each other optically:
– OLM/P11 and OLM/P12 with each other
– OLM/G11 and OLM/G12 as well as OLM/G12 EEC with each other
– OLM/G11-1300 and OLM/G12-1300 with each other
Optical channels connected via fiber-optic cables must be set to the same mode.
Transitions between different OLM types are only possible via the RS-485
interface.
In the network topologies described below, the OLM/G12-EEC can be used
everywhere where an OLM/G12 can be used.
SIMATIC NET PROFIBUS, Optical Link Module
Operating Instructions, 07/2008, A2B00065774O, Edition V1.5
Point-to-point connection
Bus (linear) topology
Star topology
Redundant optical ring
3