Accessories

8 Accessories

8 .1 Air connection set

Specially machined barrel nipples which ensure reliable,
correct measurement at the orifices installed in the
burner. Version /E is installed in the burner on delivery.
Designation
Air inlet pipe ECO 0 – 1 R 1 /E
Air inlet pipe ECO 2 R 1 1/2 /E
Air inlet pipe ECO 3 – 5 R 2 /E
Air inlet pipe ECO 6 R 3 /E
ECOMAX · Edition 10.17

8 .2 Air flow detector set

Order No.
22802897
22802898
The differential pressure switch for air flow monitor-
22802899
ing is used for the automatic monitoring of the air flow
22802900
on the burner ECOMAX in conjunction with the burner
control unit BCU 465. The differential pressure switch
monitors the air flow during pre-purge and burner op-
eration. If there is no air pressure, the burner is switched
off or is not enabled. The pressure switch switching
point should be set to approx. 80% of the differential
pressure in normal operation.
Designation
Air flow detector set ECO /E
Order No.
21802994