Nibe F1145-5 Installer Manual page 54

Ground source
Table of Contents

Advertisement

Menu 5.3.16 - humidity sensor
prevent condensation, syst.
Setting range: on/off
Factory setting: off
limit RH in the room, syst.
Setting range: on/off
Factory setting: off
Here you select whether your system(s) is/are to limit
the relative humidity level (RH) during heating or cooling
operation.
You can also select to limit min. cooling supply to prevent
condensation on pipes and components in the cooling
system.
See the installation instructions for HTS 40 for function
description.
Menu 5.3.22 - photovol control
affect room temperature
Setting range: on/off
Factory setting: off
affect hot water
Setting range: on/off
Factory setting: off
Here you set whether you want EME 10 to affect the
room temperature and / or the hot water.
See the accessory installation instructions for function
description.
Menu 5.4 - soft in/outputs
Here you state where the external switch function has
been connected to the terminal block, either to one of
5 AUXinputs or to utgång AA3-X7.
Menu 5.5 - factory setting service
All settings can be reset (including settings available to
the user) to default values here.
NOTE
When resetting, the start guide is displayed the
next time the heat pump is restarted.
Menu 5.6 - forced control
You can force control the different components in the
heat pump and any connected accessories here.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function
in any other way may cause damage to the
components in your climate system.
54
Chapter 8 |
Control - Menus
Menu 5.7 - start guide
When the heat pump is started for the first time the start
guide starts automatically. Start it manually here.
See page 32 for more information about the start guide.
Menu 5.8 - quick start
It is possible to start the compressor from here.
Caution
There must be a heating or hot water demand
to start the compressor.
Caution
Do not quick start the compressor too many
times over a short period of time as this may
damage the compressor and its surrounding
equipment.
Menu 5.9 - floor drying function
length of period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2 days
Factory setting, period 4: 3 days
temp. period 1 – 7
Setting range: 15 – 70 °C
Default value:
temp. period 1
temp. period 2
temp. period 3
temp. period 4
temp. period 5
temp. period 6
temp. period 7
Set the function for under floor drying here.
You can set up to seven period times with different cal-
culated flow temperatures. If less than seven periods are
to be used, set the remaining period times to 0 days.
Mark the active window to activate the underfloor drying
function. A counter at the bottom shows the number of
days the function has been active. The function counts
degree minutes as during normal heating operation but
for the supply temperatures that are set for the respect-
ive period.
NOTE
During under floor drying, the heating medium
pump in 100% runs, regardless of the setting in
menu 5.1.10.
20 °C
30 °C
40 °C
45 C
40 °C
30 °C
20 °C