Nibe F1145-5 Installer Manual page 49

Ground source
Table of Contents

Advertisement

"cooling" (accessory required) means operating mode
cooling for the heating medium pump.
If there are accessories for cooling present or if the heat
pump has a built-in function for cooling you can also set
the heating medium pump speed during active respect-
ively cooling operating modes (the heating medium
pump then runs in manual operation).
Menu 5.1.12 - internal electrical addition
max connected el. add.
Setting range: 7 / 9
Default value: 7
set max electrical add.
Setting range: 0 - 9 kW
Factory setting: 6 kW
fuse size
Setting range: 1 - 200 A
Factory setting: 16 A
transformation ratio
Setting range: 300 - 3000
Factory setting: 300
Here you set the max. electrical output of the internal
electrical addition in F1145 and the fuse size for the in-
stallation.
Here you can also check which current sensor is installed
on which incoming phase to the property (this requires
current sensors to be installed, see page 26). Check by
marking "detect phase order" and pressing the OK but-
ton.
The results of these checks appear just below the menu
selection "detect phase order".
Menu 5.1.14 - flow set. climate system
presettings
Setting range: radiator, floor heat., rad. + floor heat.,
DOT °C
Default value: radiator
Setting range DOT: -40.0 – 20.0 °C
Factory setting DOT: -18.0 °C
own setting
Setting range dT at DOT: 0.0 – 25.0
Factory setting dT at DOT: 10.0
Setting range DOT: -40.0 – 20.0 °C
Factory setting DOT: -18.0 °C
The type of heating distribution system the heating
medium pump (GP1) works towards is set here.
dT at DOT is the difference in degrees between flow and
return temperatures at dimensioned outdoor temperat-
ure.
NIBE F1145
Menu 5.1.22 - heat pump testing
NOTE
This menu is intended for testing F1145 accord-
ing to different standards.
Use of this menu for other reasons may result
in your installation not functioning as intended.
This menu contains several sub-menus, one for each
standard.
Menu 5.2 - system settings
Make different system settings for the heat pump here,
e.g. master/slave settings, docking settings and which
accessories are installed.
Menu 5.2.1 - master/slave mode
Setting range: master, slave 1-8
Default value: master
Set the heat pump as master- or slave unit. In systems
with one heat pump it must be "master".
Caution
In systems with several heat pumps each pump
must have a unique name, that is only one heat
pump can be "master" and only one for example
can be "slave 5".
Menu 5.2.2 - installed slaves
Set which slaves are connected to the master heat pump.
There are two ways of activating connected slaves. You
can either mark the alternative in the list or use the
automatic function "search installed slaves".
search installed slaves
Mark "search installed slaves" and press the OK button
to automatically find connected slaves for the master
heat pump.
NOTE
Before these settings are made, each slave must
have received a unique name (see menu 5.2.1).
Menu 5.2.3 - docking
Enter how your system is docked regarding pipes, for
example to pool heating, hot water heating and building
heating. The menu is only displayed if at least one slave
is connected to the master.
TIP
Examples of docking alternatives can be found
at www.nibe.eu.
This menu has a docking memory which means that the
control system remembers how a particular reversing
valve is docked and automatically enters the correct
docking the next time you use the same reversing valve.
Chapter 8 |
Control - Menus
49