Menu 5.1.9 - brine pump speed
op. mode
Setting range: auto / manual / fixed delta
Default value: auto
delta T
Setting range: 2 - 10 °C
Factory setting: 4 °C
speed in wait mode
Setting range: 1 - 100 %
Factory setting: 70 %
manual
Setting range: 1 - 100 %
Factory setting: 100 %
speed active cooling (accessory is required)
Setting range: 1 - 100 %
Factory setting: 70 %
speed passive cooling (accessory is required)
Setting range: 1 - 100 %
Factory setting: 100 %
Set the speed of the brine pump here. Select "auto" if
the speed of the brine pump is to be regulated automat-
ically (factory setting) for optimal operation.
For manual operation of the brine pump deactivate
"auto" and set the value to between 1 and 100%.
For operation of brine pump with "fixed delta", select
"fixed delta" under "op. mode" and set the value
between 2 and 10 °C.
If there are accessories for cooling present or if the heat
pump has a built-in function for cooling you can also set
the brine pump speed during passive cooling operation
(the brine pump then runs in manual operation).
Menu 5.1.10 - op. mod heat med pump
op. mode
Setting range: auto, intermittent
Default value: auto
Set the operating mode of the heating medium pump
here.
auto: The heating medium pump runs according to the
current operating mode for F1145.
intermittent: The heating medium pump starts approx.
20 seconds before and stops at the same time as the
compressor.
48
Chapter 8 |
Control - Menus
Menu 5.1.11 - pump speed heating medium
Operating status
Setting range: auto / manual
Default value: auto
Manual setting, hot water
Setting range: 1 - 100 %
Default values: 70 %
Manual setting, heating
Setting range: 1 - 100 %
Default values: 70 %
Manual setting, pool
Setting range: 1 - 100 %
Default values: 70 %
wait mode
Setting range: 1 - 100 %
Default values: 30 %
max. allowed speed
Setting range: 50 - 100 %
Default values: 100 %
speed active cooling (accessory is required)
Setting range: 1 - 100 %
Default values: 70 %
speed passive cooling (accessory is required)
Setting range: 1 - 100 %
Default values: 70 %
Set the speed at which the heating medium pump is to
operate in the present operating mode. Select "auto" if
the speed of the heating medium pump is to be regu-
lated automatically (factory setting) for optimal opera-
tion.
If "auto" is activated for heating operation, you can also
make the setting "max. allowed speed" which restricts
the heating medium pump and does not allow it to run
at a higher speed than the set value.
For manual operation of the heating medium pump,
deactivate "auto" for the current operating mode and
set the value to between 0 and 100% (the previously set
value for "max. allowed speed" no longer applies).
"heating" means operating mode heating for the heat-
ing medium pump.
"wait mode" means heating or cooling operating modes
for the heating medium pump but when the heat pump
has neither a need for compressor operation nor electric-
al addition and slows down.
"hot water" means operating mode hot water for the
heating medium pump.
"pool" (accessory required) means operating mode pool
heating for the heating medium pump.