Siemens SINAMICS G List Manual page 646

Table of Contents

Advertisement

Faults and Alarms
List of faults and alarms
A35223 (F, N)
TM: ZM offset not permissible
Reaction:
NONE
Acknowledge:
NONE
Cause:
The entered zero mark offset is not permissible.
Fault value (r0949, decimal):
1: Zero mark offset is too high.
See also: p4426
Remedy:
Enter the zero mark offset in the permissible range (p4426).
Reaction upon F:
OFF1 (NONE, OFF2, OFF3)
Acknowledge
IMMEDIATELY (power on)
upon F:
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
A35801 (F, N)
TM DRIVE-CLiQ: Sign-of-life missing
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ communications error has occurred between the control unit and the terminal module involved.
Alarm value (r2124, hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.
Remedy:
- check the DRIVE-CLiQ connection.
- replace the component involved.
See also: p9916
Reaction upon F:
NONE
Acknowledge
IMMEDIATELY
upon F:
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
A35802 (F, N)
TM: Time slice overflow
Reaction:
NONE
Acknowledge:
NONE
Cause:
Time slice overflow on terminal module.
Remedy:
Replace the terminal module.
Reaction upon F:
NONE
Acknowledge
IMMEDIATELY (power on)
upon F:
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
A35803 (F, N)
TM: Memory test
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred in the RAM test on the terminal module.
Remedy:
- check whether the permissible ambient temperature for the terminal module is being maintained.
- replace the terminal module.
Reaction upon F:
NONE
Acknowledge
IMMEDIATELY (power on)
upon F:
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
3-646
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004