B23 Conventional Flue Installations - Lochinvar EcoForce EF80 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

B23 C
ONVENTIONAL
8.8.1
B
conventional flue system components
23
When installing as a fan assisted conventional flue appliance models EF80-EF120 require a Twin-pipe conversion kit and additionally require
an Air inlet guard as below.
Model
EF80
EF100,EF120
When installing as a fan assisted conventional flue appliance models EF150-EF180 are factory supplied in a Twin-pipe configuration so only
require an Air inlet guard as below
Due to the large Flue pipe size required Lochinvar does not supply conventional flue components for models EF150,
EF180 except the air inlet guard. For this installation type a flue system designer/installer should be consulted.
8.8.2
Maximum length – conventional/twin-pipe flue
The maximum length of the flue system is determined by the resistance of the components within the flue When a conventional or twin-pipe
flue is to be used, the maximum length of the flue system is limited by the combined resistance of the inlet (if used) and outlet flue components
as detailed in the following tables.
The resistance must not exceed 200 Pa.
The information shown in table 8.6.12 is for the Lochinvar supplied flue system only; other flue system suppliers
may have different values.
F
I
LUE
NSTALLATIONS
Conversion kit Item number
Model
EF150
EF180
B
23
FLUE SYSTEM SPECIFICATION
MANUFACTURER MUELINK & GROL
TEMPERATURE CLASS T120
FLUE GAS MATERIAL PP
VARIOUS FLUE ITEMS ARE AVAILABLE SEE FLUE ASSEMBLY AND
ANCILLARIES GUIDE AT
E61-001-163
E61-001-164
WWW.LOCHINVAR.LTD.UK
Air Inlet guard Item number
M73039
M86787
Air Inlet guard Item number
M81660
M81660
34