CONTROL OPTIONS AND SETTINGS

W
H
O
ATER
EATER
PTIONS
0-10V DC remote flow temperature set point
The hot water temperature is controlled by connecting an external 0-10V DC signal to the water heater (connections 15-16).
P5BB Analogue input Config (0=off 1=temp) (display D1).
This parameter must be set at "1" so the supplied 0-10 V dc signal will control the temperature set point.
Possible settings are:
0 =
0-10V control off
1 =
0-10V temperature set point control active
See also the following graph for the relation between the temperature and the control signal.
P2GB off
Values for illustration purposes, programmed parameter values can deviate!
P2GA on
P2GC max.
0-10 Vdc control signal
P2GD offset Legionella
P5CI hysteresis Legionella
P5CD Legionella temperature
P6CA max. Temperature set point
e.g. 90°C
P5CH min. temperature set point
e.g. 20°C (default)