Flue Terminal Location - Lochinvar EcoForce EF80 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

F
T
L
LUE
ERMINAL
OCATION
8.3.1
Flue
positions
Location
8.3.2
Flue terminal minimum distances
*Any termination of a room sealed appliance shall be in such a position as will not cause a hazard to the health of persons who may be nearby
or a nuisance to other persons beyond the curtilage. The height to the centreline of the terminal shall not be less than 2m from occupied
external areas.
Detailed recommendations for the flue system are given in BS5440-1 for equipment of rated input not exceeding 70kW net, BS6644 for
equipment above 70kW net and IGE/UP/10 for equipment of rated input above 54kW net. The following notes are intended to give general
guidance only.
Description
A
Directly below an opening, air brick, opening windows etc.
B
Above an opening, air brick, opening windows etc.
C
Horizontally to an opening, air brick, opening windows etc.
D
Below a gutter or sanitary pipework
E
Below the eaves
F
Below a balcony or car port roof
G
From a vertical drain or soil pipe
H
From an internal or external corner
I
Above ground, roof or balcony level
J
From a surface facing the terminal
K
From a terminal facing the terminal
L
From an opening in the car port (e.g. door, window) into the dwelling
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the same wall
P
From a vertical structure on the roof
Q
Above intersection with the roof
terminal
EF80 – EF180
2000
960
960
75
200
200
144
300
300*
960
2000
1160
1440
577
300
300
18