Air Supply; Combustion Ventilation; Cooling Ventilation; Mechanical Ventilation - Lochinvar EcoForce EF80 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

AIR SUPPLY

The following information is based on single Water heater installations only. If more than one Water heater is being used, BS6644 should be
consulted to calculate the necessary requirements.
C
V
OMBUSTION
ENTILATION
When used as a Type C appliance, ventilation for combustion is not necessary as the combustion air is ducted directly from outside.
When used as a Type B appliance, the combustion air requirements are as follows:
Gross
Input
Model
(kW)
EF80
82.2
EF100
102.2
EF120
123.3
EF150
153.3
EF180
184.3
9.1.1
Combustion ventilation requirements – EF80 – EF180
C
V
OOLING
ENTILATION
When used as a type C appliance, installed in a compartment or an enclosure, cooling ventilation should be provided as follows:
Input
(Gross)
Model
kW
EF 58
62.2
EF80
82.2
EF100
102.2
EF120
123.3
EF150
153.3
EF180
184.3
9.2.1
Cooling ventilation requirements
When used as a type B appliance, provision for cooling ventilation is included in the combustion ventilation allowance.
M
V
ECHANICAL
ENTILATION
In situations where combustion air cannot be provided by the means of ventilation grilles, it can be supplied by a fan. The minimum flow rate
for the fan should be in accordance with Table 9.4.
If required, extract air can also be through the use of a fan. When sizing the extract fan, the extract flow rate should be calculated by subtracting
the difference volume (from Table 9.4) from the actual supplied volume of inlet air. If therefore, a larger than required inlet volume is provided,
the extract flow rate will need to be increased accordingly.
If the ventilation discharge from the plant room is through the means of simple openings relying on thermal effects, the minimum free areas of
the openings and any associated grilles should be as specified for natural ventilation (see Section 9.1:). The ventilation openings shall be at
high level and the air supply shall be at low level.
Ventilation must not be provided through natural inlet and mechanical extract as this will cause a negative pressure
within the plant room and may lead to the products of combustion being drawn into the plant room.
Appliance Type
Without draught diverters.
(with or without draught stabilisers)
9.3.1
Mechanical ventilation flow rates
Low
Summer Use
Net
Input
High
Low
High
(kW)
(cm
)
(cm
)
(cm
2
2
74.0
148
296
92.0
184
368
111.0
222
444
138.0
276
552
166.0
332
664
Enclosure/Compartment
(Direct to Outside)
Input
(Net)
High
kW
(cm
56.0
277
74.0
370
92.0
458
111.0
555
138.0
690
166.0
830
Plant Room
Medium
High
Summer Use
Summer Use
Low
High
Low
)
(cm
)
(cm
)
(cm
2
2
2
222
370
296
444
276
458
368
552
333
555
444
666
414
690
552
828
498
830
664
996
Low
)
(cm
)
2
2
277
370
458
555
690
830
Flow rate per kW total rated net input (m
Minimum Inlet Air
(Combustion, Ventilation)
2.58
Enclosure
Low
Summer Use
Summer Use
High
Low
High
)
(cm
)
(cm
)
(cm
2
2
2
370
740
444
458
920
552
555
1110
666
690
1377
828
830
1658
996
Enclosure/Compartment
(To Internal Space)
High
Low
(cm
)
(cm
)
2
2
558
558
740
740
920
920
1110
1110
1377
1377
1658
1658
/h)
3
Difference between Inlet and Extract Air
(Inlet minus Extract Ventilation)
Medium
High
Summer Use
Low
High
Low
)
(cm
)
(cm
)
(cm
)
2
2
2
2
814
518
888
1012
644
1104
1221
777
1332
1518
966
1656
1826
1162
1992
Water heater Room
High
Low
(cm
)
(cm
)
2
2
N/A
N/A
148
148
184
184
222
222
276
276
332
332
1.35 ± 0.18
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents