Adjustment Values - Lochinvar EcoForce EF80 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

A
DJUSTMENT VALUES
To make adjustments easier, values of table 1 are presented in the following figures.
The CO
/ O
values should always be between the values set in this figure. Nominal values can be found in the
2
2
Technical specifications datasheet at the beginning of this manual. All values are measured without front door.
21.2.1
Gas type G20
The CO
level must not be in the hatched area.
2
EF80 - EF180
____________________________________________________________________________
21.2.2
Propane G31:
Fan settings must be changed by altering parameter P4BD (display D8). (Only by a Competent Engineer).
The CO
level must not be in the hatched area.
2
EF80 - EF120
CO
2
9.2 %
max load
9.0 %
8.7 %
min load
8.5 %
CO
2
10,5 %
max load
10,3 %
9,3 %
min load
9,1 %
adjust
O.K.
adjust
adjust
O.K.
adjust
adjust
O.K.
adjust
adjust
O.K.
adjust
O
2
4.5 %
4.8 %
5.4 %
5.7 %
O
2
4,9 %
5,2 %
6,7 %
7,0 %