Panel Specification - ABB Eurofire EN54 User And Engineers Instructions

Combined conventional and alarm sense fire detection and alarm control panel
Table of Contents

Advertisement

Panel Order Code
No. of Zones
(25 detectors per zone max)
No. of alarm lines
Maximum alarm load
Auxiliary outputs
Inputs
Display
Mains input voltage
Output d.c. voltage
Battery size
Panel aesthetics
Panel dimensions (mm) hwd
Standby duration
Detector units
* For networking please specify the isolated CAN Network driver.
Alarm Sense (2-Wire) Specification.
Product code
No. of zones
Detectors per zone
Sounders per zone
Sounder current
Sounders per panel
Inputs
Display
Mains input voltage
DC output auxiliary voltage
Battery size
Battery standby
Panel dimensions (mm) hwd
Programmable features
CAN Network
Ancillary outputs:
Alarm Lines
Alarm current total
Auxiliary outputs
Fault outputs
Notes.
[1] – Current is dependent on sound level and tone outputs. Total current must not exceed 80 high output sound
levels. Or 200 low output sound levels.
[2] – Alarm lines – AL1 to AL4.
[3] – Total Panel Alarm Current is 1.25A, therefore zone sounder current must be taken into account when
deciding how much loading is allowed on Alarms AL1 to AL4.
Alarmsense is a registered trade name of Apollo Fire Detectors Ltd.

PANEL SPECIFICATION

FEUN-4
FEUN-8
4 Zone
8 Zone
conventional /
conventional /
2wire
2wire
4 (expandable to 16 programmed in groups of 4)
Total = 1.25A. Maximum per line or circuit = 1A
Two sets of volt-free aux. programmable contacts (rated 2A @ 30V d.c.)
Two sets of volt-free fault contacts (rated 2A @ 30V d.c.)
Class change, Bomb Alert and Programmable
4 x 20 character LCD + zone fire and fault LED's
230Vac + 10%, -6%. 50Hz
24V d.c. @ 250mA,
12V 7AH x 2 (connected in SERIES)
Metal back box with moulded polycarbonate front panel in cool grey
Minimum 24 Hours (please contact technical sales for further information.)
Apollo 60 and Orbis series smoke and heat with diode base. 220-680 Ohm call-
FEWN-4
FEWN-8
4 Zone
8 Zone
25 maximum
25 maximum
25 maximum
25 maximum
Low
Medium
4ma
8ma
200
160
Class change, Bomb Alert, Programmable
4 x 20 character LCD + zone fire & fault LED's and system LED's
230 vac = 10% -6% 50Hz
24V d.c. @ 250mA,
12V d.c @ 250mA
12V 7AH x 2 (connected in SERIES)
Minimum 24 Hours (please contact technical sales for further information.)
469 x 373 x 103
Extensive via buttons and LCD display
Panel and repeater combinations via CAN 2.0b link
4
Is 1.25A-Zone Sounder Current
2 sets of volt free contacts, rated @ 2A 30Vdc
2 sets of volt free contacts, rated @ 2A 30Vdc
FEUN-12
12 Zone
conventional /
2wire
12V d.c @ 250mA
469 x 373 x 103
point
FEWN-12
12 Zone
25 maximum
25 maximum
High
16ma
80
22
FEUN-16
16 Zone
conventional /
2wire
FEWN-16
16 Zone
25 maximum
25 maximum
note [1]
note [1]
note [2]
note [3]