To alter a Conventional zone in to a TwoWire (Alarm Sense) zone, for example Zone 2:-
-
Remove Link J11 – This will ensure that the correct voltage is put on to the zone 2.
Through option 23. → 23 SET ZONE CONFIG, Set the configuration of Zone 2 to TwoWire.
-
-
If sounders have been installed onto the zone, alarm patterns will have to be created so that the
sounders activate in a fire condition:-
Through option 16 - → 16 EDIT PATTERN – Create a pattern that will activate zone 2 sounders.
-
Pattern
Zone 2 Sounder
→Pattern Details
Item
NetAdd→ 0 Delay
Pulse
Pattern time CONT
Item
Through option 17 - → 17 ASSIGN ZN PTTRNS – Assign this pattern to all zones.
-
To alter a zone to Conventional from Two wire – for example change zone 2 to Conventional from TwoWire.
-
Insert link into J11 – This will put the correct voltage on to zone 2 for conventional detectors.
Through option 23. → 23 SET ZONE CONFIG, Set the configuration of Zone 2 to Conventional.
-
Through option 16 - → 16 EDIT PATTERN and option 17 → 17 ASSIGN ZN PTTRNS – Check
-
that the patterns for zone 2 are still correct and valid – They may require modifying or removing.
→ 24 ENTER ZONE TEXT
This function allows text to be entered against each of the available zones. The text is one line of 20 characters
which is displayed on the LCD when there is a fire condition on the zone.
Edit Zone 1 Text?
Zone 1 TEXT
Edit
When button 3 Edit is selected, will bring up the editing menu:-
Editing Zone 1 Text?
Zone 1 TEXT
^
When editing the last character (20
4
Edit
Exit
0
0 On1 Off0
Up
Dwn
Back
The sounder will now activate when any zone goes into fire.
Up
Dwn
Exit
Up
Dn
th
), the (→) display changes to 'EXIT'. This will return you to the previous menu.
33
Ensure that Zone 2 Sounder is selected in
the pattern.
Then edit the pattern details so that the
sounder will operate as required, for
example, sound until reset:-
See below:-
NetAdd 0 – To ring locally on the panel.
Delay = 0 Seconds.
Pulse time = 0 Seconds.
(alarms will not be pulsed)
Durn = CONT (sounder will be activated
until panel is reset or silenced)
On time = 0 sec Off time = 0sec.
Button 3 – Edit will allow you to edit
the text shown on line 2.
Button 4 – Up moves to next zone text
Button 5 – Dwn moves to previous
zone text.
Button 6 – exit returns back to menu
system saving the changes.
Button 3 – ← moves cursor (^) to
previous character.
Button 4 – Up edits character upwards.
Button 5 – Dn edits character
downwards.
Button 6 – → moves cursor (^) to next
character.