Event Log To Pc - ABB Eurofire EN54 User And Engineers Instructions

Combined conventional and alarm sense fire detection and alarm control panel
Table of Contents

Advertisement

3) The panels can now be networked to each other:- through Set up net devices
At Panel address No1, connect to it, the Panel address no2.
My Adrs 1
CONNECT?
Toggle
At Panel address No2, connect to it, the Panel address no1.
My Adrs 2
CONNECT?
Toggle
→ 28 EVENT LOG TO PC
ONLY SELECT THIS OPTION WHEN THE PC IS SET UP AND READY TO RECEIVE DATA FROM THE
PANEL. An Emergi-Lite Converter Cable is Required.
Prior to sending data to the PC, connect the Converter Cable from the 'PC PORT' connection on the Eurofire EN54
PCB to the COM port of the PC.
A program such as 'HyperTerminal' is required to connect the PC to the Eurofire EN54 panel. The settings on
'HyperTerminal' for the connection are:-
Bits Per Sec = 4800,
In 'HyperTerminal' choose the 'Transfer' tab and then select 'Capture Text', select a name and location where the file
is to be saved.
Once the PC is set up to receive data from the Eurofire EN54 panel Then select → 28 EVENT LOG TO PC
The event log will now be sent to the PC.
Mode:Star
2 = P Y
Up
down
exit
Mode:Star
1 = P Y
Up
down
exit
– This sends the event (history) log to a PC.
Data Bits = 8,
Parity = None,
41
The top line shows the address of this
panel is 1 and is connected in Isolated
Star configuration
At address 2 there is a Panel (P), which
is connected (Y) to this panel.
Pressing button3 toggle will connect /
disconnect panel2 (this is indicated by
the 'Y' or 'N'.)
The top line shows the address of this
panel is 2 and is connected in Isolated
Star configuration
At address 1 there is a Panel (P), which
is connected (Y) to this panel.
Pressing button3 toggle will connect /
disconnect panel2 (this is indicated by
the 'Y' or 'N'.)
Stop Bits = 1,
Flow Control = None.