Edit User Text; Blank; Setup Network - ABB Eurofire EN54 User And Engineers Instructions

Combined conventional and alarm sense fire detection and alarm control panel
Table of Contents

Advertisement

→ 25 EDIT USER TEXT
→ 26 Blank
→ 27 SETUP NETWORK
Networking allows the signalling of fires, faults, evacuates, and alarm ringing patterns to other Eurofire EN54 panels
and Repeater panels. Networking allows the reporting and control of information from panels located in adjacent
buildings etc.
The panel signals using a two wire (4 for repeaters – 2 power and 2 signal) interconnection based on CAN (Control
Area Network) Networking. This allows the devices to be up to 1000M apart (using the appropriate cable to meet
requirements of BS5839-1 : 2002.)
The devices that can be networked are:-
1)
Eurofire EN54 Panels
Fire:
The Eurofire EN54 will signal fires to other Eurofire EN54 panels. It will pass the panel
network address, the zone number and zone text. The panel also sends ringing
information (patterns) on the network.
The Eurofire EN54 sends ringing information (patterns) to repeater panels networked to it.
Evacuate:
Alarm patterns if programmed are sent to other Eurofire EN54 panels and Repeaters.
Class Change:
Alarm patterns if programmed are sent to other Eurofire EN54 panels and Repeaters.
Bomb Alert:
& Prog. Input:
Silence:
Alarm silence signals are sent to other Eurofire EN54 panels and Repeaters.
Resound:
Alarm resound signals are sent to other Eurofire EN54 panels and Repeaters.
Reset:
Reset signals to other Eurofire EN54 panels and Repeaters.
Fault:
The Eurofire EN54 will signal faults to other Eurofire EN54 panels and Repeaters.
It sends panel network address, zone no. if applicable, and also the nature of the fault.
2)
Eurofire EN54 repeaters
The repeater gives all visual indications and allows control of a Eurofire EN54 control panel remotely - all
user functions are available at the repeater. Contact Emergi-lite safety systems for more information.
This is the text that is displayed as the 'system healthy message '
Please refer to 'Enter Zone Text' above when editing the user text.
1) Other Eurofire EN54 panels.
34
2) Eurofire EN54 Repeaters.

Hide quick links: