Assign Zone Patterns - ABB Eurofire EN54 User And Engineers Instructions

Combined conventional and alarm sense fire detection and alarm control panel
Table of Contents

Advertisement

This would be set up as shown:-
NetAdd→ 4 Delay
Pulse
Pattern time 1890
Item
The Eurofire control panel is supplied with the following settings as default:-
Conventional - FEUN
Pattern
Device
Ptrn 0
Alarms 1,2,3,4
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 1
Alarms 1,2,3,4
(NetAdd=0; Delay=0; Pulse=CONT; On=1; Off=1; Pattern Time=CONT)
Ptrn 2
Alarms 1,2,3,4 & Auxiliary Relay Continuous
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Alarm Sense - FEWN
Pattern
Device
Ptrn 0
Alarms 1,2,3,4
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 1
Alarms 1,2,3,4
(NetAdd=0; Delay=0; Pulse=CONT; On=1; Off=0; Pattern Time=CONT)
Ptrn 2
Alarms 1,2,3,4 & Auxiliary Relay Continuous
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 3
All Zone Sounders
(NetAdd=0; Delay=0; Pulse=0; On=1; Off=0; Pattern Time=CONT)
Ptrn 4
All Zone Sounders
(NetAdd=0; Delay=0; Pulse=CONT; On=1; Off=0; Pattern Time=CONT)
In order to set up patterns:-
1)
Decide on how the pattern is to operate:-
Delays, Continuous or Pulsing, devices to be active, network address of where the pattern is to ring etc.
2)
Check what patterns are currently active on the panel – use menu options 16 'edit patterns' and 17
'assign zn pttrns'.
3)
Using option 16 'EDIT PATTERNS'.
Create the required pattern or patterns.
4)
Once all patterns have been created, assign them to the zones that they are to be activated from – use
option 17 'ASSIGN ZN PTTRNS'. Any number of patterns can be assigned to any or all of the zones.
→ 17 ASSIGN ZN PTTRNS
Assigns patterns to a zone or number of zones. When a fire is detected on a zone, the patterns assigned to that
zone will operate as per the pattern programming from Option 16 EDIT PATTERN.
Selct Zone + Pattern
Zone
tggle
Please note, any or all of the patterns can be assigned to any or all of the zones.
30
90 On2 Off2
Up
Dwn
Back
Period
Continuous
Pulsing (1sec on/off)
Period
Continuous
Pulsing (1sec on/off)
Continuous
Pulsing (1sec on/off)
1 Pattern 0
ACTIVE
Zup
Pup
exit
Netadd = network address No4 (where
the pattern will be activated.)
Delay = 30 Seconds.
Pulse time = 90 Seconds.
(alarms will be pulsed for 90-30=60 sec)
At a rate of :-
On time = 2 sec Off time = 2sec.
Pattern Time = 1890
(which is 1890-90=1800sec or 30mins).
Where Assigned to
Evacuate & Class Change
Bomb Alert
All Zones
Where Assigned to
Evacuate & Class Change
Bomb Alert
All Zones
All Zones, Evacuate, Class Change
Bomb Alert
Shows that when Zone 1 is in fire
Pattern 0 will Activate.
Button 3 – tggle will make the pattern
Active or Unused for that zone.
Button 4 – Zup moves to next zone.
Button 5 – Pup moves to next pattern.
Button 6 – exit returns back to menu
system saving the settings at same time.
30