MENY 5.3.12 - EXHAUST/SUPPLY AIR
MODULE
lowest extract air temp.
Setting range: 0 – 10 °C
Default value: 5 °C
bypass at excess temperature
Setting range: 2 – 10 °C
Default value: 4 °C
bypass during heating
Setting range: on/off
Factory setting: off
cut-out value, exh. air temp.
Setting range: 5 – 30 °C
Default value: 25 °C
months btwn filter alarms
Setting range: 1 – 24
Default value: 3
lowest extract air temp.: Set the minimum extract air
temperature to prevent the heat exchanger freezing.
bypass at excess temperature: If a room sensor is in-
stalled, set the excess temperature at which the bypass
damper is to open here.
months btwn filter alarms: Set how often the filter alarm
is to be displayed.
See the installation instructions for ERS for function
description.
MENU 5.3.14 - F135
charge pump speed
Setting range: 1 – 100 %
Factory setting: 70 %
hot water at cooling
Setting range: on/off
Factory setting: off
Here you can set the charge pump speed for F135. You
can also choose to charge hot water with F135 at the
same time as the outdoor section produces cooling.
Caution
It is necessary for "active cooling 4 pipe" to
be selected in either "accessories" or "soft
in/outputs" to enable activation of "hot water
during cooling". The heat pump must also be
activated for cooling operation.
60
Chapter 8 | Control - Menus
MENU 5.3.15 - GBM COMMUNICATION
MODULE
start diff additional heat
Setting range: 10 – 2,000 DM
Factory setting: 400 DM
hysteresis
Setting range: 10 – 2,000 DM
Factory setting: 100 DM
Make settings for the gas boiler GBM 10-15 here. For
example . you can select when the gas boiler is to start.
See the accessory installation instructions for a descrip-
tion of function.
MENU 5.3.16 - HUMIDITY SENSOR
climate system 1 HTS
Setting range: 1–4
Default value: 1
limit RH in the room, syst.
Setting range: on/off
Factory setting: off
prevent condensation, syst.
Setting range: on/off
Factory setting: off
Up to four humidity sensors (HTS 40) can be installed.
Here you select whether your system(s) is/are to limit
the relative humidity level (RH) during heating or cooling
operation.
You can also choose to limit min. cooling supply and
calculated cooling supply to prevent condensation on
pipes and components in the cooling system.
See the Installer Manual for HTS 40 for function descrip-
tion.
MENU 5.3.18 - POOL
Here you select which pump to use in the system.
MENU 5.3.19 - ACTIVE COOLING 4 PIPE
Here you select which pump to use in the system.
NIBE VVM 310