Nibe VVM 310 EMK Installer Manual page 55

Indoor module
Hide thumbs Also See for VVM 310 EMK:
Table of Contents

Advertisement

Sub-menus
Menu
SERVICE
has orange text and is intended for the
advanced user. This menu has several sub-menus.
Status information for the relevant menu can be found
on the display to the right of the menus.
operating settings
Operating settings for the indoor
module.
system settings
System settings for the indoor module,
activating accessories etc.
accessory settings
Operational settings for different
accessories.
soft in/outputs
Setting software controlled in and out-
puts on the input circuit board (AA3).
factory setting service
Total reset of all settings (includ-
ing settings available to the user ) to default values.
forced control
Forced control of the different compon-
ents in the indoor module.
start guide
Manual start of the start guide which is run
the first time when the indoor module is started.
quick start
Quick starting the compressor.
NOTE
Incorrect settings in the service menus can
damage the installation.
MENU 5.1 - OPERATING SETTINGS
Operating settings can be made for the indoor module
in the sub menus.
MENU 5.1.1 - HOT WATER SETTINGS
economy
Setting range start temp. economy: 5 – 55 °C
Factory setting start temp. economy: 46 °C
Setting range stop temp. economy: 5 – 60 °C
Factory setting stop temp. economy: 49 °C
normal
Setting range start temp. normal: 5 – 55 °C
Factory setting start temp. normal: 49 °C
Setting range stop temp. normal: 5 – 60 °C
Factory setting stop temp. normal: 52 °C
luxury
Setting range start temp. lux: 5 – 70 °C
Factory setting start temp. lux: 55 °C
Setting range stop temp. lux: 5 – 70 °C
Factory setting stop temp. lux: 58 °C
Here you set the start and stop temperature of the hot
water for the different comfort options in menu 2.2.
NIBE VVM 310
MENU 5.1.2 - MAX FLOW LINE
TEMPERATURE
climate system
Setting range: 5-80 °C
Default value: 60 °C
Set the maximum supply temperature for the climate
system here. If the installation has more than one cli-
mate system, individual maximum supply temperatures
can be set for each system. Climate systems 2 - 8 can-
not be set to a higher max supply temperature than cli-
mate system 1.
Caution
Underfloor heating systems are normally
flow line temperature
°C.
Check the max floor temperature with your
floor supplier.
MENU 5.1.3 - MAX DIFF FLOW LINE TEMP.
max diff compressor
Setting range: 1 – 25 °C
Default value: 10 °C
max diff addition
Setting range: 1 – 24 °C
Default value: 7 °C
Here you set the maximum permitted difference
between the calculated and actual supply temperature
during compressor respectively add. heat mode. Max
diff. additional heat can never exceed max diff. com-
pressor
max diff compressor
If the current supply temperature exceeds the calculated
supply by set value, the degree minute value is set to
0. The compressor in the heat pump stops if there is
only a heating demand.
max diff addition
If "addition" is selected and activated in menu 4.2 and
the current supply temperature exceeds the calculated
temperature by the set value, the additional heat is
forced to stop.
Chapter 8 | Control - Menus
max
set between 35 and 45
55